Type: AJT AMP-TRAP 2000R
Characteristic: low breaking capacity class J TD
Rated current: 1A-600A
Rated voltage: 600V AC and 500V DC
Rated breaking capacity: 600V AC - 200kA, 500V DC - 100kA
Standards: IEC 60269-2-1, UL/CSA 248.8, Rendition DC - UL 198L
|
|
|
|
Type: A4BQ (class L TD)
Characteristic: low breaking capacity
Rated current: 100-6000A for AC
and 100-3000A for DC
Voltage: 600V AC and DC
Rated breaking capacity: 200kA for AC and 100kA for DC
Sizes: |
100-600A |
measurement: |
51x219 mm |
|
601-800A |
|
63x219 mm |
|
801-1200A |
|
63x273 mm |
|
1201-1600A |
|
76x273 mm |
|
1601-2000A |
|
89x273 mm |
|
2001-2500A |
|
114x273 mm |
|
2501-3000A |
|
127x273 mm |
|
3001-4000A |
|
146x273 mm |
|
4001-5000A |
|
159x273 mm |
|
5001-6000A |
|
181x273 mm |
Standards: UL 248-10, CSA C22.2 no. 248.10, DC UL St. 198L
|
|
|
|
Type: A2D and A6D (class RK1 TD)
Characteristic: low breaking capacity
Rated current: 0,1A-600A
Voltage: 250 and 600 V AC
Max. breaking current: 200 (300) kA
Sizes: |
|
250V |
|
600 V |
0-30A |
|
14x51 mm |
|
21x127 mm |
31-60A |
|
21x76 mm |
|
27x139 mm |
61-100A |
|
27x149 mm |
|
34x200 mm |
101-200A |
|
40x181 mm |
|
46x244 mm |
201-400A |
|
53x219 mm |
|
66x295 mm |
401A-600A |
|
66x264 mm |
|
80x340 mm |
Standards: UL 248-12, CSA 22.2 no. 248.12
|
|
|
|
Type: ATDR
Characteristic: low breaking capacity class CC TD
Rated current: 0,25A-30A
Rated voltage: 600V AC and 300V DC
Rated breaking capacity:
600V AC - 200kA, 300V DC - 100kA
Sizes: 10x38 (10,4x38,1 mm)
Standards: UL/CSA 248.4, Rendition DC - UL 198L
|
|
|
|
Type: ATQR AMP-TRAP 2000R
Characteristic: low breaking capacity class CC TD
Rated current: 0,1A-30A
Rated voltage: 600V AC
Rated breaking capacity: 200kA
Sizes: 10x38 (10,4x38,1 mm)
Standards: UL/CSA 248.4
|
|
|
|
Fuses TRI-ONIC
Type: TR and TRS (class RK5 TD)
Characteristic: low breaking capacity
TR
AC: 0,1A-600A 250V AC, 200 kA
DC: 0,1A-2 0,8A and 35A-400A,
250 V DC, 20 kA,
3A-30A & 450A-600A,160VDC, 20kA
TRS
AC: 0,1A-600A, 600V AC, 200 kA
DC: 0,1A-12 A, 600V DC, 20 kA
70A-600A, 600V DC, 100 kA
15 - 60 A, 300 V DC, 20 kA
Standards: UL 248-12, CSA C22.2 no. 248.12,
DC according to UL 198L
Sizes: |
|
250V |
|
600 V |
|
0-30A |
|
14x51 mm |
|
21x127 mm |
|
31-60A |
|
21x76 mm |
|
27x139 mm |
|
61-100A |
|
27x149 mm |
|
34x200 mm |
|
101-200A |
|
40x181 mm |
|
46x244 mm |
|
201-400A |
|
53x219 mm |
|
66x295 mm |
|
401A-600A |
|
66x264 mm |
|
80x340 mm |
|
|
|
|
|
Fuses TRI-ONIC
Type: TRS-RDC (DC according to TD)
Characteristic: low breaking capacity DC
Rated current:
1A-30A /300V DC
35A-400A /600V DC
Max. breaking current: 20 kA
Sizes: |
0-30A |
|
measurement: |
21x127 mm |
|
|
31-60A |
|
|
27x139 mm |
|
|
61-100A |
|
|
34x200 mm |
|
|
101-200A |
|
|
46x244 mm |
|
|
201-400A |
|
|
66x295 mm |
|
Standards: MSHA no. 28-26-0
|
|
|
|
Fuses AMP-TRAP
Type: A4J (class J FA)
Characteristic: rapid
Rated current: 1A-600A
Voltage: 600V AC and 300V DC
Max. breaking current: AC 200 kA, DC 20 kA
Sizes: |
1-30A |
|
measurement: |
21x57 mm |
|
|
31-60A |
|
|
27x60 mm |
|
|
61-100A |
|
|
29x117 mm |
|
|
101-200A |
|
|
41x146 mm |
|
|
201-400A |
|
|
54x181 mm |
|
|
401A-600A |
|
|
64x203 mm |
|
Standards: UL 248-8, CSA C22.2 no. 248.8,
DC according to UL198L. EC 269-2-1
|
|
|
|
Fuses AMP-TRAP
Type: A4BY (class L)
Characteristic: low breaking capacity
Rated current:
200 - 6000 A /600V AC,
200 - 2500 A /300V DC,
Voltage: 600V AC and 300V DC
Max. breaking current: AC 200 kA, DC 100 kA
Sizes: |
200-600A |
|
measurement: |
51x219 mm |
|
|
601- 800A |
|
|
63x219 mm |
|
|
801-1200A |
|
|
63x273 mm |
|
|
1201-1600A |
|
|
76x273 mm |
|
|
1601- 2000A |
|
|
89x273 mm |
|
|
2001- 2500A |
|
|
114x273 mm |
|
|
2501- 3000A |
|
|
127x273 mm |
|
|
3001- 4000A |
|
|
146x273 mm |
|
|
4001- 5000A |
|
|
159x273 mm |
|
|
5001- 6000A |
|
|
181x273 mm |
|
Standards: for applications of 601-6000A: UL 248-10, DC UL St. 198L, CSA
C22.2 no. 248.10
|
|
|
|
Fuses AMP-TRAP
Type: A4BT (class L TD)
Characteristic: low breaking capacity
Rated current: 200A-2000 A
Voltage: 600V AC, 500V DC
Max. breaking current:
AC 200 kA, DC 100 kA
Sizes: |
200-600A |
|
measurement
| 51x219 mm |
|
|
601- 800A |
|
|
63x219 mm |
|
|
801- 1200A |
|
|
63x273 mm |
|
|
1201-1600A |
|
|
76x273 mm |
|
|
1601- 2000A |
|
|
89x273 mm |
|
Standards: for applications of 601-2000A: UL 248-10, DC UL St. 198L, CSA C22.2 no. 248.10
Applications: motors, transformers, panelboards, mains
|
|
|
|
Fuses AMP-TRAP
Type: A3T and A6T (class T FA)
Characteristic: rapid
A3T
1A-1200A 300V AC, 200 kA
1A-1200A 160V DC, 50 kA
A6T
1A-800A 600V AC, 200 kA
1A-800A 300V DC, 100 kA
Sizes: from 10,3x22,4 till 63,5x110 mm
Standards: UL 248-15, CSA C22.2 no. 248.15, DC UL St.198L
|
|
|
|
Fuses AMP-TRAP
Type: A2K and A6K (class RK1FA)
Characteristic: rapid
Rated current: 1A-600A
A2K: 250V AC and DC,
A6K: 600V AC and 300 V DC
Max. breaking current: 200 kA
Sizes: |
|
250 V |
|
600 V |
0-30A |
|
14x51 mm |
|
21x127 mm |
31-60A |
|
21x76 mm |
|
27x139 mm |
61-100A |
|
27x149 mm |
|
34x200 mm |
101-200A |
|
40x181 mm |
|
46x244 mm |
201-400A |
|
53x219 mm |
|
66x295 mm |
401A-600A |
|
66x264 mm |
|
80x340 mm |
Standards: UL 248-12, CSA C22.2 no. 248.12, DC UL St. 198L
|
|
|
|
Fuses AMP-TRAP
Type: AG (class G)
Characteristic: low breaking capacity
Rated current: 0,5A-20A /600V AC
25-60A /480 V AC
Max. breaking current: 100 kA
Sizes: |
0,5-15A |
|
10,3x33,3 mm |
|
20A |
|
10,3x35,8 mm |
|
25, 30A |
|
10,3x41,2 mm |
|
35-60 A |
|
10,3x57,2 mm |
Standards: UL ST. 248-5, CSA C22.2 no. 248.5
|
|
|
|
Type: ATMR AMP-TRAP 2000R
Characteristic: low breaking capacity class CC TD
Rated current: 0,1A-30A
Rated voltage: 600V AC
Rated breaking capacity: 200kA
Sizes: 10,4x38,1 mm
Standards: UL/CSA 248.4
Applications: transformers from 50 till 1000VA, lighting, general loads
|
|
|
|
Fuses mocy One-Time
Type: OT, OTN, OTS (class K-5)
Rated current:
OT - 1A-600A 250V AC, 50 kA,
1A-600A 250V DC, 20 kA
OTN (Canada) - 15A-60A, 250V AC, 50 kA
OTS - 1A-600A 600V AC, 50 kA
1A-600A 300V DC, 20 kA
Sizes: |
|
250V |
|
600 V |
0-30A |
|
14x51 mm |
|
21x127 mm |
31-60A |
|
21x76 mm |
|
27x139 mm |
61-100A |
|
27x149 mm |
|
34x200 mm |
101-200A |
|
40x181 mm |
|
46x244 mm |
201-400A |
|
53x219 mm |
|
66x295 mm |
401A-600A |
|
66x264 mm |
|
80x340 mm |
Standards: UL ST. 248-9, CSA C22.2 no. 248.9, DC according to UL198L,
|
|
|
|
Fuses mocy
z wymiennym topikiem
Type: RF/RFS and RL/RLS (class H)
Rated current: 1A-600A
Voltage: RF - 250 V AC, RFS- 600 V AC
Max. breaking current: 10 kA
Sizes:
Standards: UL 248-7, CSA C22.2 no. 248.7
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: ATQ 500 V AC (TD)
Characteristic: low breaking capacity
Rated current: 0,1A-30A
Voltage: 500 V AC
Max. breaking current: - 10 kA
Sizes: 10x38 mm
Standards: UL ST. 248-14, CSA C22.2 no. 248.14
|
|
|
|
Type: TRM Midget
Characteristic: low breaking capacity
Rated current: 0,1A-30A
Rated voltage: 250V AC
Rated breaking capacity: 10kA
Sizes: 10x38 mm
Standards: UL/CSA 248.4
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: GFN
Characteristic: low breaking capacity
Rated current: 0,1A-30A
Parametry: 0,1A-10A 250V AC,
12A-15A, 125V AC
20A-30A, 32V AC
Max. breaking current: 200A for 250 V
for others 10 kA
Sizes: 10x38 mm
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: A6Y-2B
Characteristic: rapid
Rated current: 0,25A-15A
Parametry: 0,25A-3A 600V AC, 3,2A-15A 500 V AC
Max. breaking current: 10 kA
Sizes: 10x38 mm
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: ATM
Characteristic: rapid
Parametry: 0,1A-50A 600V AC,
0,1A-30A 500 V DC
Sizes: 10x38 mm
Standards: for 0,1A-30A - AC
and DC: UL 248-14, CSA C22.2 no. 248.14
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: OTM
Characteristic: rapid
Rated current: 1A-30A
Voltage: 250V AC
Max. breaking current: 10 kA
Sizes: 10x38 mm
Standards: UL 248-14, CSA C22.2 no. 248.14
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: GGU
Characteristic: rapid
Rated current: 3A-30A
Voltage: 125V AC
Max. breaking current: 10 kA
Sizes: 10x38 mm
Applications: general purpose
Standards: 3 - 15 A: UL 248-14
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: SBS
Characteristic: rapid
Rated current: 0,2A-30A
Voltage: 600V AC
Max. breaking current: 100 kA
Sizes: 10x35 mm
Standards: UL 248-14, CSA C22.2 no. 248.14
(according to UL 198G and CSA 59.2)
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: PCF
Characteristic: rapid
Rated current: 1A-30A
Voltage: 600V AC and 500V DC
Max. breaking current: 100 kA
Sizes: 10x38 mm
Standards: UL
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: PCS
Characteristic: very rapid
Rated current: 5A-30A
Voltage: 600V AC and DC
Max. breaking current: AC: 200 kA, DC: 100 kA
Sizes: 10x38 mm
Applications: to protect semiconductors
Standards: UL
|
|
|
|
Fuses Cylindrical (Special purpose fuses) Midget
Type: PCT
Characteristic: low breaking capacity
Rated current: 1A-30A
Voltage: 500V AC
Max. breaking current: 100 kA
Sizes: 10x38 mm
Standards: UL
|
|
|
|