Type:
NH and NH DIN110
Characteristic: gS
Rated current: 16A-630A
Voltage: 690V AC
Rated breaking capacity: AC 100kA
Sizes: NH 1, 2, 3
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type:
NH
Characteristic: gR
Rated current: 6A-125A
Voltage: 690V AC and 440V DC
Rated breaking capacity: AC 50kA and DC 25kA
Sizes: 00C, 00, 1, 2
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type:
NH DIN80 and DIN110
Characteristic: gR
Rated current: 6A-690A
Voltage: 690V AC and 440V DC
Rated breaking capacity: AC 50kA and DC 25kA
Sizes: 00C, 00, 1, 2, 3
Standard: IEC 60269-4
Applications: for protecting semiconductors
Downloads |
JEAN MÜLLER catalog's pagesof DIN80 in English and German |
PDF,
14 pages, 1,25 MB |
JEAN MÜLLER catalog's pages of DIN110 in English and German |
PDF,
12 pages, 1,1 MB |
FERRAZ catalog's pages |
PDF,
17 pages, 950 KB |
ETI catalog's pages |
PDF,
14 pages, 900 KB |
|
|
|
|
Type:
NH
Characteristic: aR
Rated current: 6A-800A
Voltage: 690V, 1000 and 1200V AC
Rated breaking capacity: AC 200kA
Sizes: 00, 1, 2, 3
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type:
NH DIN80 and DIN110
Characteristic: aR
Rated current: 10A-1400A
Voltage: 690V and 1000V AC
Rated breaking capacity: AC 200kA
Sizes: 00C, 00, 1, 2, 3
Standard: IEC 60269-4
Applications: for protecting semiconductors
Downloads |
JEAN MÜLLER catalog's pages in English and German |
PDF,
14 pages, 1,35 MB |
JEAN MÜLLER catalog's pages DIN80 and DIN110 1000V in English and German |
PDF,
10 pages, 1,02 MB |
FERRAZ catalog's pages |
PDF,
17 pages, 950 KB |
FERRAZ catalog's pages |
PDF,
25 pages, 950 KB |
ETI catalog's pages |
PDF,
31 pages, 2,4 MB |
|
|
|
|
Type:
NH G
Characteristic: gR
Rated current: 35A-630A
Voltage: 500V and 1000V AC
Rated breaking capacity: AC 120kA
Sizes: 1, 2, 3
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type:
NH G
Characteristic: aR
Rated current: 50A-1250A
Voltage: 690V and 1000V AC
Rated breaking capacity: AC 120kA
Sizes: 1, 2, 3
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type:
PROTISTOR PSC, HLS
Characteristic: aR, gR and gRB
Rated current: 50A-3600A
Voltage: 650V-2000V AC
Sizes: 70, 71, 72, 73, 2x72, 2x73, 91, 92, 93, 2x92, 2x93,
DIN 1-3, 80, 110, 140, 210
Rated breaking capacity: 300kA
Standards: UL and IEC 60269.4
|
|
|
|
Type:
PROTISTOR PSC-LR
Rated current: 100-10000A
Voltage: 130-3800V AC
Rated breaking capacity: 100-240kA
Sizes: 30 - 2x174
Standards: IEC 60269-4
|
|
|
|
Type:
Cylindrical (Special purpose fuses)
Characteristic: aR
Rated current: 0,1A-135A
Voltage: 400V-690V AC
Rated breaking capacity: 200kA
Sizes: 10x38, 14x51 and 22x58 mm
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type: Cylindrical (Special purpose fuses)
Characteristic: gR
Rated current: 1A-125A
Voltage: 400V-690V AC
Rated breaking capacity: - 200kA
Sizes: 10x38, 14x51 and 22x58 mm
Standard: IEC 60269-4
Applications: for protecting semiconductors
|
|
|
|
Type:
Cylindrical (Special purpose fuses) 27x60
Characteristic: gR and aR
Rated current: 0,8A-135A
Voltage: 800V-1000V AC
Rated breaking capacity: 300kA
Sizes: 27x60 mm
Standards: IEC 60269-1 and 4
|
|
|
|
Type:
BS88-4
Characteristic: aR, gR, gRB
Rated current: 5A-1050A
Voltage: 250V, 500V, 690V AC
Rated breaking capacity: 200kA
Sizes: 10x28, 10x51, 17x27, 17x49, 2x17x49, 36x27, 2x36x27,
36x55, 2x36x55 mm, 000, 2000
Standards: UL, IEC 60269-1 and 4, VDE 636-23
|
|
|
|
Type:
D
Characteristic: gR
Napiecie: 500V AC, 400V DC
Rated current: 2A-100A
Rated breaking capacity: 100kA
Sizes: DII, DIII, DIV
Standards: IEC 60269-4
DIN VDE 0636 parts 23 and 33
|
|
|
|
Type:
D0
Characteristic: gR
Napiecie: 440V AC,
Rated current: 2A-100A
Rated breaking capacity: 160kA
Sizes: D01, D02, D03
Standards: IEC 60269-4
DIN VDE 0636 parts 23 and 33
|
|
|
|