Type: NH
Characteristic: gG, gF
Selectivity: fuses for 400V and 500V AC
in network 400V AC - 1:1,25, others 1:1,45
Rated current: 2A-1600A
Rated voltage: 400V, 500V, 690V and 1000V AC, 220/440V DC (tested under 110% Un)
Rated breaking capacity:
400V AC - 100kA, 500V AC - 120kA,
690V AC - 80kA; 220/440V DC - 25kA
Sizes: NH 000, 00, 0, 1, 2, 3, 4, 4a
Standards: IEC 60269-1, VDE 0636/21
Construction: Steatite body, contacts - silverplated copper, without Cd and Pb
Applications: for protecting cables, lighting, devices
Notes:a lot of versions - isolated and uninsolated grips; indicators: on top, in front, two indicators (kombi), striker. Please ask us for details.
Producer: ETI, FERRAZ, JEAN MÜLLER
|
|
|
|
Type: NH
Characteristic: aM
Rated current: 2A-1250A
Rated voltage: 500V and 690V AC
Rated breaking capacity:
500V AC - 120kA, 690V AC - 80kA
Sizes: NH 000, 00, 0, 1, 2, 3, 4a
Standards: IEC 60269-1, VDE 0636
Construction: Steatite body, contacts - silverplated copper, without Cd and Pb
Applications: motor protection
Notes: a lot of versions - isolated and uninsolated grips; indicators: at the top, striker at the bottom. Ask us for details.
Producer: ETI, JEAN MÜLLER, FERRAZ
|
|
|
|
Type: NH
Characteristic: gTr
Rated current: 72A-1443A
(for transformers 50-1000kVA)
Rated voltage: 400V AC
Rated breaking capacity: 100kA
Sizes: NH 2, 3, 4, 4a
Standards: IEC 60269-1, VDE 0636 part 2011
Construction: Steatite body, contacts - silverplated copper, without Cd and Pb
Applications: transformers protection
Notes: a lot of versions - isolated and uninsolated grips; indicators: at the top, at the front.
Breaking: at 1,3xIn > 10h, at 1,5xIn < 2h
Producer: JEAN MÜLLER
|
|
|
|
Type: NH DC
Characteristic: DC
Rated current: from 160 till 800A
Rated voltage: 80V DC
Rated breaking capacity: 50kA
Sizes: NH 00
Standards: IEC EN 60269, VDE 0636
Construction: Steatite body, contacts - silverplated copper, without Cd and Pb
Notes: uninsolated contacts
Producer: JEAN MÜLLER
|
|
|
|
Type: NH
Characteristic: gL/gG
Rated current: 6A-630A
Rated voltage: 1200V AC
Rated breaking capacity: 50kA
Sizes: NH 1, 2, 3
Standards: IEC EN 60269, VDE 0636
Construction: Steatite body, contacts - silverplated copper, without Cd and Pb
Applications: for protecting cables, lighting, devices
Notes: uninsolated contacts; indicators: at the top, striker at the bottom
Producer: JEAN MÜLLER
|
|
|
|
Type: NH
Characteristic: gPv
Rated current: 63A-315A
Rated voltage: 110V DC
Sizes: NH 1, 2, 3
Standards: IEC EN 60269-4
Construction: Steatite body, contacts - silverplated copper, without Cd and Pb
Applications: fuses for photovoltaic applications
Notes: uninsolated contacts
Producer: JEAN MÜLLER
|
|
|
|
Type:
Service fuse
Characteristic: gL/gG, gTr
Rated current: 231A-1250A
Voltage: 400V AC
Sizes: NH 1-4a
Downloads
|
JEAN MÜLLER catalog's pages NH with current transformer in English and German |
PDF,
7 pages, 312 KB |
JEAN MÜLLER catalog's pages applications of service fuse in English and German |
PDF,
4 pages, 250 KB |
|
|
|
|
Type:
Cylindrical (Special purpose fuses)
Characteristic: gF/gG, gL/gG and aM
Voltage: 400V, 500V and 690V AC
Rated current: 0,25A-125A
Rated breaking capacity: 20-120kA
Wymiary: 8x32, 10x38, 14x51, 22x58 mm
Rendition: with/without indicator
Standards: IEC 60269-2-1, NFC 63.213 and UNE 21.103
Applications: Industry
|
|
|
|
Type: D0
Characteristic: gG and aM
Rated current: 2A-100A
Rated voltage: 400V and 250V DC
Rated breaking capacity: 50kA
Sizes: DIN 49522:
D01, D02 and D03
Standards: IEC 60269-3-1, VDE 0636 part 41 and 301
Applications: for low-voltage devices, for service by non-qualified personnel
Notes: Screw caps and gauge rings systems prevets installing wrong type fuses.
Low power loss.
|
|
|
|
Type: D
Characteristic: gL/gG and gF
Selectivity: when FS fuse links used, in same conditions 1:1,25; moreover 1:1,6
Rated current: 2A-200A
Rated voltage: 500V and 690V, 750V
and 1200V AC, 750V DC
Rated breaking capacity: DII-DV: 50kA AC
and 8kA /DC, NDZ: 4kA /AC and 1,6kA /DC
Sizes: according to DIN 49360, 49515
and 49369 - DII, DIII, DIV, DV and NDZ
Standards: IEC 60269-1, 3 and 3-1, VDE 0636 part 10, 30 and 31
Applications: for low-voltage devices, for service by non-qualified personnel
Notes: Screw caps and gauge rings systems prevets installing wrong type fuses.
|
|
|
|
Type: BS88-2
Characteristic: gG
Rated current: 2A-800A
Rated voltage: 415V AC and 250V DC
Rated breaking capacity: 80kA
Sizes: A1 - A4, B1 - B4,
C1 - C3, F1 - F2
Standards: IEC 60269-2 and BS 88-2
Applications: for low-voltage devices, lighting, condensers, batteries
Notes: admittance of Asta20
|
|
|
|
Type: BS88-2
Characteristic: gM
Rated current: 20A-315A
Rated voltage: 415V AC
Rated breaking capacity: 80kA
Sizes: A1 - A4X, B1 - B3, F1
Standards: IEC 60269-2 and BS 88-2
Applications: motor protection
Notes: admittance of Asta20
|
|
|
|
Type: MASTERFUSE
Characteristic: gG
Rated current: 1250A-4800A
Rated voltage: 690V AC
Rated breaking capacity: 160kA
Standards: IEC 60269-1 and 2
|
|
|